HIK-AL-S Eca

Power cable 0,6/1 kV with Al conductors, XLPE insulated, with halogen-free sheath

APPLICATION

Halogen-free UV resistant cable for fixed installation in buildings, channels, tubes, in open air and in the ground. The insulation must not be exposed to UV light. Installed acc. to The Danish Heavy Regulations

Construction

Conductors: : Al, class 2 according to EN 60228
Insulation: XLPE compound
Bedding: Extruded elastomere or plastomere
compound or plastic tape
Sheath: Halogen-free compound

Tehnical characteristics

CPR: Eca
Test voltage: 4 Kv
Rated voltage: 0,6/1 kV
Bending radius (min): multicore – 15D
Min. laying temperature: -0°C to 50°C
Max. short-circuit temperature: 250°C
Working temperature: -40°C to 90°C
Fire properties: EN 60332-1-2
Low smoke: acc. to EN 61304


Country: Denmark, Finland, Norway, Sweden
Industry: Building & Construction, Transmission, Distribution & Power Networks
Standard: HD 603 S1, IEC 60502-1, p.5B
Type: Fire Performance Cable, LSZH Cable, Power Network & Local Distribution Cable
Conformitè EuropëenneIECREACHROHS

Share with friends