AXMK-PE
XLPE insulated and PE sheathed power cables, rated voltage 0,6/1 kV
APPLICATION
In earth, ducts, on support brackets, in dry and wet conditions etc., where one does not expect mechanical damages and the cables are not exposed to the mechanical tensile strain. In urban networks, industrial plants, electric power plants and other electricity consumers and for connection of control devices in industry, traffic etc.
Construction
Conductors: Al, class 1 or class 2 according to
EN 60228, annealed
Insulation: XLPE compound
Bedding: Extruded filling compound or plastic tape
Outer sheath: PE compound, UV resistant
Tehnical characteristics
CPR class: Fca
Test voltage: 4 kV AC, 50 Hz, 5 min.
Rated voltage: 0,6/1 kV AC (1,5 kV DC)
Min. bending radius: multicore- 10D, D – overall
diameter
Min. laying temperature: -15°C
Max. conductor operating temperature: 90°C
Max. short-circuit temperature: 250°C
Environment operating temp.: -35°C to +3
Core marking: acc. to HD 308 S2
4-core: Green/Yellow, Brown, Black, Gray or
Blue, Brown, Black, Gray
5-core: Green/Yellow, Blue, Brown, Black, Gray or
Blue, Brown, Black, Gray, Black
Or by customer request
Country: Finland
Industry: Building & Construction, Transmission, Distribution & Power Networks
Standard: HD 603 S1, SFS 4879
Type: Instrumentation Cable, Power Network & Local Distribution Cable