HMH Dca

Halogen-free installation cables 300/500 V

APPLICATION

Halogen-free and environmentally friendly cables for fixed installation in dry and damp areas, as well as outdoors and in the open air. May be bricked in and embedded directly. Not suitable for embedment in vibrated concrete. Conductor insulation must be protected against light exposure. Installation to be performed by a qualified electrician only.

Construction

Conductors:Cu, class 1 (1,5 – 4 mm2)
Class 2 (> 4 mm2) according to EN 60228
Insulation: XLPE halogen – free compound
Bedding: 1,5–2,5 mm2–filling sheath > 4 mm2–EPDM rubber
Sheath: Gray HFFR compound, UV resistant

Tehnical characteristics

CPR class: Dca – s1,d2,a1
Test voltage: 1,5 -2,5 mm², 2000 V
4 -16 mm², 4000 V
Rated voltage: 1,5 -2,5 mm² 300/500 V
4 – 16 mm² 0,6/1 kV
Bending radius (min): 10 D
Temp. for cable laying: -15°C do +50°C
Max. working temperature: 90°C
Max. short-circuit temperature: 250°C
Smoke density: EN 61034-2
Flame retardant: EN 60332-1-2
Halogen free: EN 60754-1/2


Country: Bosnia and Herzegovina, Croatia, Denmark, Finland, Greece, Norway, Serbia, Sweden
Industry: Building & Construction, Transmission, Distribution & Power Networks
Standard: DIN VDE 0250-215, HD 603 S1, IEC 60502-1, p.5B
Type: Fire Performance Cable, LSZH Cable, Power Network & Local Distribution Cable