RZ1-K BLACK
Power cable 0,6/1 kV AC (1,5 kV DC) with Cu conductors, XLPE insulated and HFFR sheathed
Application
Power cable suitable for fixed installation in dry and damp environment, on or under plaster, on cable trays, same as in walls and concrete. Suitable for laying in ground. For outdoor application can be laid in tubes, but in that case should be taken all precautionary measures necessary to prevent water penetration into the tubes. Suitable for supply systems in an emergency. Appropriate for application in all situations where people and material goods need to be protected in case of fire. Recommended for public buildings frequented by a lot of people, and for buildings of high material value, for industrial complexes, electric power plants, transformer stations, municipal facilities, hotels, shopping malls, hospitals, schools, airports, underground railways and similar. Concentric conductor serves as electromagnetic screen, which could also be applied as neutral conductor. Expected lifetime 50 years, provided proper installation, load and ambient temperature.
Construction
Conductors: Cu, class 5 according to EN 60228
Insulation: XLPE compound, type DIX 3
Bedding: Extruded elastomere or plastomere LSZH compound
Sheat: LSZH compound, type DMZ-E
CABLE IS UV RESISTANT
Technical characteristics
CPR class: B2ca- s1a, d1, a1
Test voltage: 3,5 kV AC, 50 Hz, 5 min. per core
Rated voltage: 0,6/1 kV
Bending radius (min): 5xD, D-overall diameter
Min. service temperature:-40°C
Min. installation and handling temp.: -15°C
Max. cond. operating temp.: 90°C
Max. short-circuit temperature: 250°C
Low smoke emitting: EN 61034-2
Halogen free: EN 60754-1;
EN 60754-2
Vertical flame spread: EN IEC 60332-3-24
Flame propagation: EN 60332-1-2
CPR class: EN 50575, EN 13501-6
Country:
Industry: Building & Construction, Data Centres, Mining, Drilling & Tunnelling, Transmission, Distribution & Power Networks
Standard: HD 604 5D, IEC 60502-1, UNE 21123-4
Type: