U-1000 R2V

Power cables with XLPE insulation and PVC sheath

APPLICATION

These cables for energy distribution are suitable for all types of low voltage industrial-type connection, in urban grids, building installations, etc. Particularly suited in cases of high operating temperature and when high resistance to solar radiation and atmospheric agents is required. Good resistance to low temperature and chemical agents. Can be used without additional mechanical
protection in the open air, fixed to walls or in raceways, inside walkways, and in empty in Cable Constructions in general. Can be laid underground with mechanical protection constructed from slabs, tiles, or bricks. They are not recommend to lay this cable In ground flooded for more than two months per year. With appropriate mechanical protection it can be use in areas subject to
risk of explosion, but in this case the permitted current load is reduced by 15%. It can be used in ambient temperature down to -25°.

Construction

Conductors: Cu rope
Insulation: XLPE compound
Bedding: Extruded elastomere or plastomere
compound or plastic tape
Sheath: PVC compound

Tehnical characteristics

CPR class: Eca
Test voltage: 4 Kv
Rated voltage: 0,6/1 kV
Bending radius (min): multi-core 8D
Min. laying temperature: -10°C
Max. conductor temperature: 90°C
Max. short-circuit temperature: 250°C


Country: France
Industry: Building & Construction, Transmission, Distribution & Power Networks
Standard: IEC 60502-1, NF C32-321
Type: Industrial Cable, Power Network & Local Distribution Cable
Conformitè EuropëenneCPRCSTB NFEZUIECREACHROHS

Share with friends