N2XCH

Power cable 0,6/1 kV with Cu conductors, XLPE insulated and HFFR sheathed

Application

Distribution power cable for static outdoor application (with protection against direct UV-irradiation), in ground, in water, within facilities, in cable canals, in concrete, in conditions where there is a danger of possible mechanical damages, but where the cable is not exposed either to systematic mechanical stress or heavier tensile strain. Used in electric power plants, transformer stations, industrial plants, metropolitan networks and other electric plants. Concentric conductor can be used as neutral, protective or earth connection, and in situations where the insulation might be roughly damaged by some metal object, it acts as protection against contact voltage. Corrugated, concentric conductor construction enables establishing of several cable connections without cutting of conductor.

Construction

Conductors: Cu, class 1 or 2 according to EN 60228

Insulation: XLPE compound

Bedding: Extruded elastomere or plastomere compound or plastic tape

Concentric conductor: Cu wires with counter helix of Cu tape

Sheath: HFFR compoun

Technical characteristics

Voltage rating (Uo/U): 0,6/1 kV
Testing voltage: 4 kV
Min. temp. for cable laying: -5°C
Max. working temperature: 90°C
Max. short-circuit temperature: 250°C
Min. bending radius: single-core – 15D; multicore – 12D
CPR classification: Dca – s1,d2,a1
Fire properties: EN 60331-2, EN 60332-3-24 (cat. C)

 


Country: Austria, Croatia, Germany, Slovakia
Industry: Building & Construction, Data Centres, Transmission, Distribution & Power Networks
Standard: Cat. C, EN 60332-3-24, HD 604 5D, HD 604 S1, IEC 60502-1, VDE 0276-604
Type:
Conformitè EuropëenneCPRIECREACHROHS

Share with friends