(N)YCY
Medium voltage cable 3,6/6 kV with copper (Cu) conductor, PVC insulated and sheathed
Application
Medium voltage cable for outdoor installation, with protection against direct UV radiation, suitable for installation in ground, water, cable ducts, and concrete. It is intended for use in conditions where there is a risk of mechanical damage, but not for continuous mechanical stress or higher tensile loads.
The concentric conductor may be used as a neutral, protective, or earthing conductor. In the event of insulation damage caused by external metallic objects, it provides protection against touch voltage.
Construction
Conductor: Copper, class 2, according to EN 60228
Bedding: Extruded elastomere or plastomere
compound or plastic tape
Concentric conductor: Copper wires with counter-
helical copper tape
Sheath: PVC compound, red, UV resistant
Technical characteristics
Voltage rating (U₀/U): 3,6/6 kV
Test voltage: 11 kV
Minimum installation temperature: -5 °C
Maximum operating temperature: 70 °C
Maximum short-circuit temperature: 160 °C
Minimum bending radius: 15 D (D = outer diameter)
Flame propagation: EN 60332-1-2
Country: Austria, France, Germany
Industry: Transmission, Distribution & Power Networks
Standard: IEC 60502-2, VDE 0276-620
Type: Medium Voltage Cable